There are no translations available.
Dimensions of the steel Flanges DN 500 - 20"
n° - number of holes dia - diameter of bolts
Flange standard |
PN Rating |
D |
K |
L |
n° |
dia |
c |
d |
f |
UNI 2223 DIN 2501 BS 4504 NF E 29-203* ISO/DIS 7005-1.2* |
2,5-6 |
645 |
600 |
22 |
20 |
M20 |
28 |
570 |
4 |
10 |
670 |
620 |
26 |
20 |
M24 |
28 |
585 |
4 |
16 |
715 |
650 |
33 |
20 |
M30 |
36 |
610 |
4 |
25 |
730 |
660 |
36 |
20 |
M33 |
44 |
615 |
4 |
40 |
755 |
670 |
42 |
20 |
M39 |
52 |
615 |
4 |
64 |
800 |
705 |
48 |
20 |
M46 |
68 |
590
|
4 |
100 |
870 |
760 |
56 |
20 |
M54 |
94 |
590
|
4
|
ISO/DIS 7005-1.2 NF E 29-203 |
20 |
700 |
635 |
32,5 |
20 |
M30 |
43,0 |
584,5 |
2 |
50 |
775 |
686
|
35,5 |
24 |
M33 |
63,5 |
584,5 |
2 |
100 |
815 |
724 |
45,0 |
24 |
M42 |
89,0 |
584,5 |
7** |
ANSI B 16.5 BS 1560 |
150 |
27,50 (698,5) |
25,00 (635,0) |
1,25 (31,7) |
20 |
1,12 (28,6) |
1,69 (17,5) |
23,00 (584,2) |
0,06 (1.6) |
300 |
30,50 (774,7) |
27,00 (685,8)
|
1,38 (34,9) |
24 |
1,25 (31,8) |
2,50 (63,5) |
23,00 (584,2) |
0,06 (1,6) |
400 |
30,50 (774,7) |
27,00 (685,8) |
1,62 (41,3) |
24 |
1,50 (38,1) |
2,75 (69,8) |
23,00 (584,2) |
0,25** (6,4) |
600 |
32,00 (812,8) |
28,50 (723,9) |
1,75 (44,4) |
24 |
1,62 (41,3)
|
3,50 (88,9) |
23,00 (584,2) |
0,25** (6,4) |
900 |
33,75 (857,2) |
29,50 (749,3) |
2,12 (54,0)
|
20 |
2,00 (50,8) |
4,12 (107,9)
|
23,00 (584,2) |
0,25** (6,4) |
BS 10 AS 2129 |
A |
27¾ (704,9) |
25¼ (641,4) |
1 (25,4) |
12 |
⅞ (22,2) |
1 (25,4) |
— |
— |
D |
27¾ (704,9) |
25¼ (641,4) |
1 (25,4) |
16 |
⅞ (22,2) |
1¼ (31,8) |
— |
— |
E |
27¾ (704,9) |
25¼ (641,4) |
1 (25,4) |
16 |
⅞ (22,2) |
1¼ (31,8) |
— |
— |
F |
29 (736,6)
|
26½ (673,1) |
1¼ (31,8) |
24 |
1⅛ (28,7) |
1½ (38,1) |
— |
— |
H |
29 (736,6) |
26½ (673,1) |
1¼ (31,8) |
24 |
1⅛ (28,7) |
2 (50,8) |
23½ (596,9) |
1/16 (1.6) |
J |
29 (736,6) |
26½ (673,1) |
1⅜ (34,9) |
24 |
1¼ (31,8) |
2½ (63,5)
|
23½ (596,9) |
1/16 (1.6) |
Note - The dimensions of ANSI - BS -AS flanges are in inch; the others are in mm (the ones in brackets included which are derived from the dimensions in inch)* For ratings 2,5-6-10-16-25-40 only** To be added to the thickness C of the flange
|